How to size Current Transformers? - Energy Advice (2024)

Selection of optimal current transformer for specific application should evaluate not only transformer voltage level, turns ratio and accuracy, but also accuracy limit factor. This allows to avoid critical measurement errors due to transformer core saturation. The rated accuracy limiting factor is the ratio of the rated accuracy limit primary current to the rated primary current. For example, 5P10 transformer accuracy limit factor is 10. This means than current transformer will measure with less than 5% error, when primary current is not bigger than 10 times the rated nominal current. However, 10 for this transformer is rated accuracy limit factor. In practical applications, design engineer should calculate real accuracy limit factor, that will depend on the transformer installation conditions.

In order to add current transformer in EA-PSM, user should first draw the single line diagram and add breaker element on the line, where he wants to connect the current transformer.

How to size Current Transformers? - Energy Advice (6)

Double click on the breaker icon, open the “Equipment” and “Current transformer” tabs. Push “Add” button, to add current transformer. When current transformer is added, user can specify its parameters.

Some of the parameters needed for ALF calculation EA-PSM will take automatically from the load flows and short circuits calculation results, therefore, user should make sure that these calculations are done, and all network parameters are specified correctly.

How to size Current Transformers? - Energy Advice (7)

Here user should specify “CT type” and “Coefficient” of the current transformer.

Wire loop length should be calculated according to the CT connection type (4- or 6- wire connection). The difference between 4 and 6 wire schemes is depicted below.

How to size Current Transformers? - Energy Advice (8)

For example, if distance between the current transformer and relay is 5 meters, then in case of 6 wire connection wire loop length should be taken as 2 x 5 = 10 m and only 1,2 x 5 = 6 m for 4 wire connection. Other parameters that software need to calculate resistance of the wire is “Wire cross section” and “Wire material”. User should specify this data to represent real installation conditions of the transformer.

“PN” is nominal power of the transformer and “Internal resistance” is internal resistance of the transformer. These parameters should be taken from the transformer specifications. IED load is internal resistance of the connected relays.

Test case

We need to select current transformer for 10kV feeder. Short circuit current is 6897 A. Nominal current from load flows calculation is 345 A. According to nominal current, we will first try 600/1 ratio current transformer.

The recommended minimal accuracy limiting factor can be calculated from the formula:

How to size Current Transformers? - Energy Advice (9)

Here Inis current transformer nominal current, Isis short circuit current and over – dimensioning factor. Most commonly KTFis used 1,2 – 2. For example, in our case with KTF= 2, Frmin=23.

In order to select the right rating of the current transformer, we will have to iterate for the solution by making a guess of the nominal ALF. Other information we are going to need for this calculation: wire length 20 m, cross section area 5 mm2, wire material is copper, Sn=5 VA, Rct=11 Ohm, Rload= 0,5 Ohm.

First, we will try with 5P10 current transformer.

How to size Current Transformers? - Energy Advice (10)

Fris actual accuracy limiting factor. Usually actual accuracy limiting factor is higher than nominal ALF as CT is normally under – burdened. However, from the results we see, that Fr< Frmintherefore, we should take CT with bigger nominal ALF.

In the second iteration we will take 5P20 rating and assume that other parameters are the same.

How to size Current Transformers? - Energy Advice (11)

Now Fr< Frmintherefore 5P20 is good for our application.

The main drawback of this method is that user do not know what KTFvalue to take and what value is sufficient. For example, breaker tripping time is critical factor in selecting KTFas faster fault disconnection time will not allow CT to saturate. For this reason, it is recommended to use EA-PSM current transformer sizing function, that uses more advanced CT sizing method. Formulae for KTFis provided below:

How to size Current Transformers? - Energy Advice (12)

Where parameters are as follow:

Xtj – short circuit reactance;

Rtj – short circuit resistance;

w – angular frequency equal to 314 rad/s in 50 Hz networks;

Ts – CT secondary time constant that depends on magnetizing and leakage inductance as well as secondary loop resistance. In EA-PSM we assume Ts = 1s;

Tp – short circuit DC component time constant;

t – is time to saturation. In EA-PSM we assume that t = 0,035 s for most relays this time is enough to determine the short circuit current.

How to size Current Transformers? - Energy Advice (13)

From here it is also clear that :

How to size Current Transformers? - Energy Advice (14)

therefore it is not recommended to assume KTFvalue without knowing network data.

In the analyzed case:

How to size Current Transformers? - Energy Advice (15)

Reference

  1. IEC 60044-1. Instrument transformers – Part 1: Current transformers
  2. Ziegler, Digital Differential Protection, Differential Protection Symposium, Belo Horizonte, 2005

Subscribe to our Newsletter

Receive the latest news of Digital Twins and IT solutions for energy efficiency

I am an expert in the field of energy systems and analysis, with a demonstrable understanding of various aspects related to energy audits, climate-neutral strategies, power system studies, heat networks, and production technological audits. My expertise extends to the selection and optimization of current transformers for specific applications, as well as the use of software tools like EA-PSM in this context.

In the provided article, several key concepts are discussed:

  1. Energy Advice Services:

    • Energy Audit
    • Development of a Climate-Neutral Strategy
    • Power System Studies
    • Analysis of Heat Networks and Heat Production
    • Production Technological Audit
  2. Products and Implemented Projects:

    • The article mentions the need to select the optimal current transformer for a specific application, emphasizing the importance of evaluating not only transformer voltage level, turns ratio, and accuracy but also the accuracy limit factor.
  3. EA-PSM Software:

    • The article introduces the process of adding a current transformer in EA-PSM, involving drawing a single-line diagram, adding a breaker element, and specifying transformer parameters.
  4. Current Transformer Parameters:

    • Parameters such as "CT type," "Coefficient," "Wire Loop Length," "Wire Cross Section," "Wire Material," "Nominal Power (PN)," and "Internal Resistance" are discussed as crucial for accurate current transformer representation.
  5. Test Case:

    • A practical example is presented where the goal is to select a current transformer for a 10kV feeder, considering short circuit current, nominal current, and other parameters.
  6. Accuracy Limit Factor (ALF):

    • The article provides a formula for calculating the recommended minimal accuracy limiting factor based on nominal current, short circuit current, and an over-dimensioning factor.
  7. CT Sizing Method:

    • The article mentions a more advanced current transformer sizing method in EA-PSM, considering parameters like short circuit reactance, short circuit resistance, angular frequency, secondary time constant, DC component time constant, and time to saturation.
  8. References:

    • References to standards such as IEC 60044-1 are included, providing a foundation for the discussed concepts.

In conclusion, the article provides valuable insights into the complexities of current transformer selection, emphasizing the need for careful consideration of various parameters and the use of advanced tools like EA-PSM for accurate sizing.

How to size Current Transformers? - Energy Advice (2024)
Top Articles
Latest Posts
Article information

Author: Jonah Leffler

Last Updated:

Views: 6260

Rating: 4.4 / 5 (45 voted)

Reviews: 92% of readers found this page helpful

Author information

Name: Jonah Leffler

Birthday: 1997-10-27

Address: 8987 Kieth Ports, Luettgenland, CT 54657-9808

Phone: +2611128251586

Job: Mining Supervisor

Hobby: Worldbuilding, Electronics, Amateur radio, Skiing, Cycling, Jogging, Taxidermy

Introduction: My name is Jonah Leffler, I am a determined, faithful, outstanding, inexpensive, cheerful, determined, smiling person who loves writing and wants to share my knowledge and understanding with you.